For the fire occurred in the building or other emergency situations such as emergency lighting lamps (metal halide lamps open elements, sodium) to provide centralized power supply emergency power unit.
Installation form (EPS emergency lighting power supply) :Floor type, hanging, embedded
EPS - Standby time(EPS emergency lighting power supply): 90 minutes, the national standard type (according to design requirements Configure standby time)
0.5KW—10KW Single-phase input (220V, AC) have: (Standard type) hanging:KBED—0.5KW、1KW、1.5KW、2KW Embedded:KBED—0.5KW、1KW、1.5KW、2KW Floor type: KBED—1KW、1.5KW、2KW、3KW、4KW、5KW、6KW、7KW、8KW、9KW、10W Three-phase input (380V, AC) have: (Standard type) floor type:
HBED—0.5KW、1KW、1.5KW、2KW、3KW、4KW、5KW、6KW、7KW、8KW、9KW、10KW Note: The latest national standard GB 17945-2000 "fire emergency lighting" standards for the standby time of 90 minutes.
Technical merit (EPS emergency lighting power supply)
1、Using the latest IGBT inverter technology; 2、Centralized power supply mode, no special lighting; 3、Emergency power supply, sine wave AC output voltage, constant frequency, no noise, pollution-free; 4、Can fire linkage, can be computer monitoring, fire control center; 5、Isolation transformer output; 6、LCD liquid crystal display;
Advantages (EPS emergency lighting power supply)
1、Simple design, easy construction; 2、And lower total cost, reduce investment; 3、Long life, the host life span of 20 years; 4、Maintenance-free batteries can be recycled 300-500 times; 5、Management of simple automatic instant switch, or unattended; 6、Illumination to maintain stable, reliable, easy to maintain; KBED series EPS Technical Data (EPS emergency lighting power supply)
Model KBED- |
0.5KW |
1KW |
1.5KW |
2KW |
3KW |
4KW |
5KW |
6KW |
7KW |
8KW |
9KW |
10KW |
Power(KW) |
0.5 |
1 |
1.5 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
Input |
Maximum current(A) |
3 |
7 |
13 |
20 |
25 |
30 |
35 |
16 |
20 |
25 |
28 |
30 |
Voltage(V) |
Single-phase 220V ± 25% or three-phase 380V ± 25% |
Frequency(Hz) |
50Hz±5% |
Output |
Rated current(A) |
2.2 |
4.5 |
6.8 |
9.1 |
13.6 |
18.1 |
22.7 |
27.2 |
32 |
36.4 |
41 |
45 |
Voltage(V) |
Normal: the same response time as the mains voltage: 220V ± 5% |
Frequency(Hz) |
50Hz ± 5% when the emergency is normal: the same as electricity |
Switching time |
Less than 5 seconds (special requirements, can be less than 0.25 seconds) |
Waveform |
Emergency when: sine wave; normal: the same with electricity |
Time of emergency power |
90 minutes (standard) |
Overload capacity |
120% load when normal (≥ 30S) |
Noise |
Static electricity when there is no noise <55dB (when the emergency power supply) |
Relative Humidity |
0—90% |
Ambient temperature |
-24℃—40℃ |
Altitude |
2000 meters |
To adapt to the load |
Mainly used for lighting and other load class |
Weight(kg) |
60 |
130 |
180 |
210 |
360 |
410 |
510 |
620 |
700 |
780 |
850 |
940 |
Output circuit |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
EPS qualifying time for the emergency lighting and lamps, switches, wiring method (EPS emergency lighting power supply)
Output line |
Description |
Wiring Methods |
Code |
Color |
L |
Red |
City when an electric power output, there is no power output of electricity (with emergency power supply) |
Ⅰ |
L1 |
Yellow |
There is no mains power output, there is no power output of electricity (with emergency power supply) |
Ⅱ |
L2 |
Green |
City when an electric power output, radio without electricity output (no emergency power supply) |
Ⅲ |
L3 |
|
City when an electric power output, electricity-free power output from the fire control have |
Ⅳ |
|
|
Electricity and electricity can be opened relations, electricity-free emergency power output (with emergency power supply) |
Ⅴ |
N |
Blue |
|
|
PE |